Skip to product information
1 of 2

Mac Afric

230V 20kVA Water Cooled Diesel Generator DPGP/20SA

230V 20kVA Water Cooled Diesel Generator DPGP/20SA

Powered by FAW 4DW91-29D, the DPGP/20SA delivers 20kva Prime Power (PRP). Coupled to a single bearing AVR controlled brushless self-excited alternator. Deepsea Manual/AMF Control Panel. Integrated ATS (Auto Transfer Switch) and many more features detailed below.

  • Powered by FAW 4DW91-29D engine
  • Coupled to a single bearing, AVR controlled brushless self-excited alternator
  • Deepsea Manual / AMF Control Panel.
  • Integrated ATS (Auto Transfer Switch).
  • Configured with 3-pole MCCB.
  • Cable entry points on the side panel.
  • Anti-vibration supports coupled between the engine/alternator and the base structure.
  • Wiring according to IEC standard.
  • Sturdy modular canopy with powder coating and soft sound attenuation that does not deform when the entire structure is raised.
  • Mild steel residential exhaust muffler with asbestos inferior to stainless steel.
  • Heavy duty powder coated steel base frame with integrated day fuel tank including filler/filter and fuel sender.
  • Central lifting points and forklift holes are provided to easily maneuver the generator set into the installation position.
  • Full load testing is performed at 50%, 75% and 100% as well as comprehensive FAT (factory acceptance testing).
  • A complete set of operation and maintenance manuals and circuit wiring diagrams are supplied with the unit.

Specifications

Power factor

Partner 4-pole alternators are designed to operate between 0.8 and 1 power factor. The alternator will be derated when operating below 0.8 power factor.

Assessment

Rating is at sea level and a 5% - 10% derating must be allowed if the unit operates at any altitude above 1500MASL (must consider whether the engine is Turbo or Naturally Aspirated)

VAC

380-400-415V/220-230-240V (50Hz)

Prime Power (PRP)

Applicable for supplying power to varying electrical loads for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capacity is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

Emergency Standby Power (ESP)

Applicable for supplying power to varying electrical loads during power interruption from a reliable source. Emergency standby power (ESP) is in accordance with ISO 8528. Fuel stop power is in accordance with ISO3046, AS 2789, DIN 6271 and BS 5514.

Engine data
  • Manufacturer: FAW
  • Model: 4DW91-29D
  • Engine speed: 1500rpm
  • Prime Power: 21KW/28HP
  • Standby power: 23KW/30HP
  • Type: 4-cycle, in-line, 4-cylinder
  • Cooling: Water – cooled
  • Aspiration: naturally aspirated
  • Displacement: 2.54L
  • Cylinder Bore* Stroke: 90mm×100mm
  • Number of cylinders: 4
  • Compression ratio: 17:1
  • Minimum full load speed: 1500 rpm
  • Steering wheel direction and rotation: counterclockwise
  • Governance: Mechanics
Cooling system
  • Engine only coolant capacity: 6L
  • Thermostat setting temperature (range): 83-95℃
  • Max coolant temperature. allowed_standby: 104℃
Engine weight
  • 220 kg
Alternator data
  • Model: DAC 184J
  • Output power: 20 Kva
  • Rated current 0.8PF: 86A per phase
  • AVR Model: SX460
  • Phase and connection: 1 Wire Phase 2
  • Power Factor (Cos Phi): 0.8
  • Exciter Stator Resistance: 20 Ohms at 22℃
  • Maximum overspeed: 2250 Rev/Min
  • Control system: self-excited
  • Insulation class: H
  • Degree of protection: IP23
  • Voltage regulation: ± 1.0%
  • Winding cables: 12
  • Winding step: two thirds
  • Waveform distortion: No load<1.5% Linear balanced load without distortion<5.0%
  • Stator winding: Concentric double layer
  • Bearing: Single
  • Exciter rotor resistance: 0.091 Ohms PER PHASE at 22°C
Fuel consumption at different loads
  • 50% of prime power: 3 LPH
  • 75% of prime power: 4.5 LPH
  • 100% of prime power: 6 LPH
Sound Attenuating Canopy - SAT
  • The sound-attenuating canopy produced by plasma and CNC towers not only meets the requirements of residential sound control, but also ensures the correct cooling aeration required for normal operation. Generator sets can be installed outdoors to save space.
  • Modular design for ease of maintenance and access.
  • Special high temperature flame retardant sound insulation foam.
  • Door hinge and handle.
  • Mild steel plate with powder coated surface finish is used for the construction of the upper cover.
  • Soundproofing foam ranges from 40mm to 100mm depending on the degree of attenuation required.
  • Standard attenuation noise level: 75~80dB within 1m; 72~75dB within 7m.
  • The Silencer is installed inside the soundproof cover within a specially manufactured fire compartment.
  • The control panel is installed inside the cowl and has an ATS mounted assembly
Our AMF control panel uses a deep water control module

The Module is an automatic mains failure controller for generator set applications. The AMF panel is used where the local mains supply is backed up by an appropriately sized generator set. The AMF panel monitors the local supply; if this supply fails or falls outside pre-set limits, the AMF panel controls the preheat, fuel solenoid and generator set starting via relays and contacts or via the engine ECU if available.

Automatic Network Failure Control Panel
  • Deep Sea Electronic Controller 4520 with Automatic Transfer Switch
  • Emergency stop button
  • Static battery charger
  • Electronically and mechanically interlocked four-pole ATS
DSE 4520 AMF Controller Key Features
  • This module is used to monitor the mains power supply and automatically start the generator set.
  • Shutdown alarms
  • Stop/Rest – Manual – Automatic – Test – Start Functionality
LCD display measurement
  • Mains Volts (LL/LN)
  • Generator Amplifiers (L1, L2, L)
  • Generator Frequency
  • Engine operating hours
  • Plant battery voltage
  • Engine Oil Pressure (PSI and Bar)
  • Engine speed (RPM)
  • Engine temperature (degrees Celsius)
Shutdowns and failures
  • Speed ​​down/up
  • Failed to start/stop
  • High engine temperature
  • Low oil pressure
  • Collection failure
  • Under/over voltage and generator frequency
  • Under/over voltage of the power grid
  • Emergency stop

Specifications table

View full details